Reduce your voltage – reduce your electricity costs October 1st 2007 UK organisations are wasting electrical energy using too high a voltage explains
Dr Alex Mardapittas of EMS (UK)
Although The Electricity
Safety,Quality and
Continuity Regulations
2002 amended the statutory
electricity supply voltages down
from 240 volts in the UK to 230V
+10% or -6% (216V – 253V) with
effect from the 1 January 2003, an
average voltage of 242V is still
supplied (approximately 12 volts -
5% - higher than the nominal
230V).This is because as electricity
travels further away from the
distribution areas, the voltage
naturally drops and in order to
ensure that the regulations are met,
the power supplier will maintain
grid voltage towards the top end of
the limits. In addition, it is to the
suppliers benefit to supply at high
voltage as the transmission losses
are less.
Does this higher voltage matter?
Well yes it does.The higher the
voltage the higher the energy
consumption. As a rule of thumb,
reducing the voltage by 5% will
result in savings of 10%. In addition,
higher voltage tends to increase
the heat generation in motors,
reducing their life, and generally
reduces the life expectancy of
electrical equipment, including
lighting bulbs.
As the majority of electrical
equipment is designed to run at the
220V nominal which is in place in
Europe, there should be no problem
operating at the UK's 230V nominal
level. All electrical equipment is
designed using parameters such as
Voltage, Frequency, Capacity, etc.
Therefore, to ensure that these are
operating at their optimum
performance, they need to operate
as close as possible to their design
characteristics.
Transformers used in substations
on sites have a series of "tappings"
which allow the user to reduce the
output voltage in a series of 2.5%
steps to the level that is required.
Thus if the output voltage were
242V,we would normally
recommend that the transformer be
reduced one tapping at a time to
230V, however, this requires a
detailed investigation.
As an engineering consultancy,
EMS saw how many sites had
excessive voltages and were thus
spending excess on energy for no
benefit.As a result EMS developed
the PowerStar unit. PowerStar
optimises the power at a company
utilising multiple tapping
transformers.
The unit obviously has a cost
attached to it, but still gives very
good payback periods and
significant advantages over a
simple tap change at the site
transformer. In fact, sites which do
not have a dedicated HV
transformer are able to take
advantage of voltage reduction
savings, which they could not do
previously.
The PowerStar unit is designed to
reduce voltages to the UK nominal
(230V) via variable impedance
transformer technology. The
advantages are many, including
significant energy savings, reduced
current and voltage harmonic
distortions, improved power factor
and also reduced maintenance
costs with extended equipment life
due to reduced operating
temperatures and operating close
to their design characteristics.
The graph (other page)
demonstrates the energy savings
achieved using PowerStar at a
refrigerated storage depot. The
results shown are over a 24hour
period(one day without PowerStar
and one day with PowerStar).
Such savings of around 12% in
electrical energy are
commonplace. Typical installations
are at office blocks, local
government buildings,
manufacturing sites,warehousing,
refrigerated storage facilities,
hotels, hospitals and colleges or
universities.
Savings will completely depend
on the application, for example in
manufacturing, where most of the
electrical power is used in motors,
savings will be less, average 12%
while in administration type
buildings savings can be
significantly higher, average 16%.
The effect of reduced harmonic
distortion is shown below at a
printing machine electrical supply,
where the two traces are measured
concurrently either side of the EMS
PowerStar unit. Total current
harmonic distortions were
significantly reduced by almost
50%. Also on the same trial,Voltage
Harmonics were shown to have
been reduced by 10%.
Identifying the opportunity for
energy savings through voltage
reduction cannot be simpler. EMS
will issue a simple plug in logger
which records site voltages for a
continuous seven day period. If the
results are promising, then a
detailed site survey would be
undertaken, with more in depth
data logging. A fully costed
quotation with an indication of
likely savings and payback period
are then issued. More articles from EMSC (UK) Ltd: |